Alkalinity Control
Concentrated liquid alkaline product for corrosion and Calcium scale control in boilers.
Application & Uses
RXSOL-50-5002-020 provides the alkaline condition for hardness control to function correctly. Without the correct precipitation and subsequent blow down of hardness salt, scale would form. This would result in restriction in water flow, ineffective heat transfer and local corrosion. The end effect would be an inefficient boiler and ultimately component failure. RXSOL-50-5002-020 also provides the alkaline condition required for corrosion control, by neutralization of acidic gases
Dosage & Directions for Use
For optimum results dose RXSOL-50-5002-020 direct to the boiler with a RXSOL Boiler Water Treatment Dosing unit, or via the bypass pot- feeder installed in the boiler feed line.
Required dosage can be controlled by pH & alkalinity test dosage chart .
One (1) milliliter of RXSOL-50-5002-020 concentrated alkaline liquid per ton of distilled water provides 0.5 ppm of lkalinity hydrate.
Low-pressure boiler (up to 28 bars)
Add RXSOL-50-002-020 to 5 litre in feed – water, There is no any specific method can be passed through the recalculating or the main feed pipe into the stream or the hot well tank.
High – Pressure Boiler (28 to 60 bars)
Dissolve the desired volume of RXSOL-50-002-020 to 5 ltr of feed – water, which should then be passed into the stream or water drum through the chemical pump.
Note:- It can also be used as a neutralizing agent following acid cleaning with descaling materials ( RXSOL-11-1008--DC descaling Liq / RXSOL-54-1008-SA Safe Acid PWD )
Technical Specifications & Properties
Testing control procedure
- Test water sample from the water boiler as described in the direction of the Alkalinity Test Kit ( p & m Total ) http://www.rxmarine.com/Alkalinity-test-kit
- Determine the present alkalinity value expressed as ppm CaCO3 .
- Desired level of 100-150 ppm as CaCO3.
- A control test for the alkalinity of the water should be conducted after 3- 6 hours from the application.
Recommended Industrial & Shipboard Areas
Alkalinity control makes sludge in soft form, which can be easily blown down from bottom side of BOILER.
Other valuable Boiler Water Treatment Chemical product :
| RXSOL-50-5020-025 | Boiler Water Treatment Auto |
| RXSOL-40-4091-025 | Scale and Corrosion Inhibitor for Cooling Water |
| RXSOL-40-4009-025 | MICRO BIOCIDE Cooling Water |
| RXSOL-50-5002-025 | Alkalinity Control |
| RXSOL-40-2000-025 | RXSOL 2000 corrosion inhibitor |
| RXSOL-40-4009-025 | MICRO BIOCIDE Cooling Water |
| RXSOL-50-5021-025 | Hardness Control Liquid |
Product Description & Chemical Profile
RXSOL-50-5002-020 is a concentrated liquid alkaline product for corrosion and Calcium scale control in boilers.
Suitable for low-pressure boiler systems (0-32 bar), medium-pressure steam propulsion vessels (32-60 bar). And also suitable to used for high-pressure steam generating systems (60-84 bar).
Need pricing, bulk volume, or vessel delivery today?
Send us your required quantity, delivery location, or vessel IMO number. Our technical marine supply team replies within 1 hour.